Safety
Safety is competency 1.0 for a reason — it comes first. The Associate CET exam expects you to know how electricity injures, how to work on equipment safely, the fire classes, and how to respond to an incident. These are high-yield, memorizable facts; this page collects the ones the exam draws from. Sections 7–16 cover the rest of competency 1.0: first aid, fuses, the NEC and OSHA, arc flash and NFPA 70E, meter CAT ratings, RF exposure, fiber, tools, ladders and service vehicles. Section 17 is job practice.
On the exam from this page
- current kills, the heart is the vulnerable organ, and the "can't-let-go" range makes even 6–16 mA dangerous
- the person who applies the lock is the only one who removes it — and you always verify de-energization by measurement, never assume
- Class C is the electrical-fire class — use a non-conductive extinguisher (CO₂ or dry chemical)
- verify absence of voltage live-dead-live: prove the tester on a known live source, test the circuit, then prove the tester again
- MPE means maximum permissible exposure: the FCC's time-averaged RF exposure limit, in 47 CFR 1.1310
How electricity injures — it's the current
The single most important safety concept: current, not voltage, is what harms you. Voltage is what drives current through your body, but it's the amount of current and its path that determines the danger. As little as 100 mA through the chest can cause ventricular fibrillation — the most common cause of death by electric shock.
| Current through body | Typical effect |
|---|---|
| ~1 mA | Barely perceptible tingle |
| ~5 mA | Slight shock, not painful; startle reaction can cause injury |
| 6–16 mA | "Can't let go" (OSHA's let-go range) — muscles contract on the conductor |
| 17–99 mA | Extreme pain, breathing can stop, severe muscle contractions; death is possible |
| 100–2,000 mA | Ventricular fibrillation — death is likely |
| Over 2,000 mA | Cardiac arrest, internal organ damage and severe burns — death is probable |
The figures are OSHA's, for a one-second, 60 Hz shock from hand to foot, drawn from NIOSH's 1998 report on worker electrocutions. Other texts round them differently; the order of the effects is what matters.
On the exam
Why this matters: the takeaway the exam wants is that current kills, the heart is the vulnerable organ, and the "can't-let-go" range makes even 6–16 mA dangerous. Dry skin has high resistance, but sweat, cuts, or wet conditions drop it sharply — raising current for the same voltage (Ohm's law: I = V/R).Reducing the risk
Because current depends on the path and on body resistance, the practical rules all aim to keep current from flowing through you:
One hand behind your back when probing live circuits keeps current from crossing your chest hand-to-hand. Discharge capacitors before working — a charged filter capacitor in a power supply can hold a lethal charge long after power is removed. Use a GFCI on bench outlets, keep one hand in your pocket, remove rings and watches, and never work alone on dangerous equipment.
Lockout / Tagout (LOTO)
Lockout/Tagout is the procedure for making sure equipment stays de-energized while it's being serviced. You physically lock the energy-isolating device (a breaker or disconnect) in the off position and attach a tag identifying who locked it and why. Only the person who applied the lock removes it.
- Notify everyone affected that equipment is being shut down for service.
- Shut down the equipment by its normal stopping procedure.
- Isolate the energy source (open the disconnect/breaker).
- Lock and tag the isolating device in the off position with your own lock.
- Release stored energy — discharge capacitors, bleed pressure, block parts that could move.
- Verify zero energy: test that the equipment won't start and measure that voltage is actually gone.
On the exam
Exam point: the golden rule of LOTO is that the person who applies the lock is the only one who removes it — and you always verify de-energization by measurement, never assume.Fire classes & extinguishers
A technician must know which extinguisher fits which fire — using the wrong one can make things worse (water on an electrical fire is a shock and spread hazard).
Safety
The one to memorize: Class C is the electrical-fire class — use a non-conductive extinguisher (CO₂ or dry chemical). If possible, de-energize first; a "Class C" fire becomes a Class A or B once the power is off.ESD — protecting the components
Not all safety is about protecting people — Electrostatic Discharge (ESD) protects the parts. A static spark you can't even feel (hundreds of volts) can destroy or weaken sensitive devices like CMOS chips and MOSFETs. Control it with a grounded wrist strap, an ESD mat, anti-static bags, and a humidity-controlled bench.
Where static comes from (competency 1.5). Charge builds by triboelectric charging: when two materials touch and then separate, electrons move from one to the other. Walking across carpet is the classic case, and dry air makes it far worse. The ESD Association lists about 35,000 V for walking on carpet at 10–25% relative humidity, against about 1,500 V at 65–90%. Humidity lowers the charge but never removes it. Ordinary plastics, foam cups and packaging charge easily and have no place on an ESD bench.
How it damages parts. The discharge current can punch through the thin gate oxide of MOS and CMOS devices and burn out junctions and metallization. Some parts die at once, a catastrophic failure that testing usually catches. Others are only weakened: they keep working, then fail early in service. There is no practical screen for these latent defects (TI calls them "walking wounded"), so a part that still works after careless handling is not proof that it is undamaged.
| Control | How it works |
|---|---|
| Wrist strap | The main way to ground a person: it keeps you at ground potential so you can't build a charge. Its ground cord has a series resistor, most commonly 1 MΩ. Static drains through it easily, but if you touch a live circuit it limits the current through you: at 250 V AC, 250 µA. Desco rates that protection up to 250 V AC, so a strap is not shock protection on higher-voltage work. Test it daily. |
| Grounded mat and bench | A dissipative work surface tied to the bench's common ground point drains charge from parts and tools at a controlled rate. |
| Remove insulators | Grounding can't drain an insulator. Take nonessential ones (cups, wrappers, personal items) off the bench; an ionizer neutralizes the ones the job needs. |
| ESD-safe packaging | A closed shielding bag keeps charges on its outside. Don't use bags with holes or tears, and keep parts packaged until they are on the grounded bench. |
| Handling | Ground yourself before you touch a part or board, not after. |
Responding to a shock incident
Do
Cut the power first — the disconnect, breaker, or unplug. If you can't, use a non-conductive object to separate the victim from the source. Then call 911 and, if they are not breathing normally, begin CPR; if you are not trained, give Hands-Only CPR.
Don't
Never touch a person who is still in contact with a live source — you'll become a second victim. Don't use anything conductive (or wet) to move them. Don't assume "low" voltage is safe.
First aid and emergency response
Competency 1.2 asks why first aid matters so much to people who work on electrical and electronic equipment, and what an untrained helper must and must not do. Competency 1.14 asks for the emergency response to each hazard on this page.
A shock can stop the heart or breathing, and help has to start before the ambulance arrives. OSHA's power-line standard shows how seriously that is taken: 29 CFR 1910.269, which covers electric power generation, transmission and distribution work, requires people with first-aid training, which includes CPR, wherever its crews work on exposed lines or equipment energized at 50 V or more: at least two at a field location with two or more workers, and at a fixed site such as a substation, enough that anyone exposed to shock can be reached within 4 minutes. Most bench work falls under OSHA's general first-aid rule instead: 1910.151 requires a trained first-aider when no clinic or hospital is close by, and eyewash or drench facilities wherever corrosive material, such as battery acid, can reach the eyes or body. Telecommunications work, including two-way radio field installations, also falls under 1910.268, which requires first-aid training that includes instruction in artificial respiration (1910.268(c)(3)).
Safety
If you are not trained: make the scene safe before you touch anyone (power off, or move the source away with a dry, non-conducting object such as wood, plastic or cardboard), call 911 and send someone for an AED, and do only what you know how to do. The American Heart Association's Hands-Only CPR, for someone who suddenly collapses, is two steps: call 911, then push hard and fast in the center of the chest, 100–120 compressions a minute.| Emergency | What to do (call 911 for anything serious) |
|---|---|
| Electric shock | Turn the power off; if you can't, move the source with a dry non-conducting object. Never touch the person while they are still in contact. Call 911 for a high-voltage contact, burns, confusion, trouble breathing, heart-rhythm problems or unconsciousness. Start CPR if there are no signs of circulation, and don't move the person unless they are in immediate danger. Stay at least 20 ft from high-voltage lines that may be live, and farther if they are sparking. |
| Thermal burn (iron, hot part) | Run cool, not cold, water over it for about 10 minutes. Take off rings or anything tight before swelling starts. Don't pop blisters, and don't use butter, oil or toothpaste. For a major burn, call 911 and cover it loosely with a clean, dry cloth or sterile gauze. |
| Electrical or arc-flash burn | Always get emergency medical help: the current went through the body, not just the skin. Make sure the power is off first. Cover burns with sterile gauze or a clean cloth, not a towel or blanket, whose fibers stick to the wound. |
| RF burn or RF shock | Stop the exposure first (have the transmitter unkeyed or shut down, or move out of the field), then treat it as a burn and report it. NIOSH recommends that RF burns and shocks be reported. |
| Chemical in the eye (battery acid) | Gently flush the eye with cool or lukewarm water for 20 minutes or until help arrives, then call Poison Help (800-222-1222 in the US) for further instructions. |
| Sliver or fiber in the eye | Don't rub the eye. Try to flush the object out with a gentle stream of clean, warm water. If it won't flush out or is embedded, don't try to remove it; get emergency care. |
| Fall from a ladder or roof | Suspect a spinal injury after a hard impact to the head or back, or with neck or back pain, numbness or weakness. Call 911 and keep the head and neck still; don't move the person. If CPR is needed, don't tilt the head back. |
Fuses and circuit breakers
Competency 1.4 asks for the fusing and breaker rules and the reasons for the different fuse types. A fuse or breaker protects the wiring and the equipment from overcurrent. It does not protect you: a 15 A breaker is built to carry 15 A, and the 100 mA that can stop a heart is less than 1% of that. Protection for people comes from GFCIs, which trip at about 5 mA of leakage, and from safe practice. Every fuse carries four ratings:
| Rating | What it means and the rule |
|---|---|
| Current rating | The current it carries continuously. Fuses are heat-sensitive, so Littelfuse recommends running them at no more than 75% of the rating (at 25 °C); a hot location shortens their life. |
| Voltage rating | The highest circuit voltage it can safely interrupt. It must be equal to or greater than the circuit voltage: a 250 V fuse is fine in a 120 V circuit, a 32 V automotive fuse is not. AC and DC ratings are separate: DC has no current zero to help put out the arc, so on a DC plant or battery string use a fuse whose maker publishes a DC rating for that voltage. |
| Interrupting rating | The largest fault current it can clear without rupturing (also called breaking capacity). It must meet or exceed the fault current available where it is installed; a fuse asked to clear more can burst instead of opening cleanly. |
| Speed | Fast-acting fuses open quickly on any overload. Time-delay (slow-blow) fuses have a thermal delay that rides through a short start-up surge, then still open on a sustained overload. |
That is why there are different types. A motor, a transformer or a capacitor-input power supply draws a large inrush current at switch-on, so a fast-acting fuse there blows every time the unit starts: it needs a time-delay fuse of the same current rating, with a voltage rating equal to or greater than the circuit voltage. A load with no inrush, or parts that can't survive even a short overcurrent, gets a fast-acting fuse. A meter's current input is the extreme case: use only the high-energy fuse its maker specifies. If you must pull or install a fuse whose terminals are energized, OSHA requires fuse-handling equipment insulated for the circuit voltage (1910.335(a)(2)(i)(A)).
On the exam
Exam point: replace a fuse only with the same type and current rating, and a voltage rating equal to or greater than the circuit voltage; never up-size the current rating. A bigger fuse lets the wiring overheat before it opens, and OSHA forbids modifying overcurrent protection even temporarily (29 CFR 1910.334(b)(3)). When a breaker trips or a fuse blows, find out why before restoring power: OSHA prohibits repeatedly resetting a breaker or replacing fuses into an unchecked fault (1910.334(b)(2)).Codes and rules: the NEC and OSHA
The NEC (competency 1.3). NFPA 70, the National Electrical Code, is the installation rulebook. NFPA revises it every three years (the 2026 edition replaced 2023), but an edition has legal force only where a state or city adopts it, and adoption varies: in 2026, Texas and New York enforce the 2023 NEC while Pennsylvania enforces 2020. The local authority having jurisdiction (AHJ) inspects the work. In practice a technician complies by knowing which edition and local amendments apply where they work; by using listed equipment and installing it as its listing instructions say, which the NEC makes mandatory (110.3(B)); by using the cable listing the space requires (plenum or riser, see Cabling); and by never altering overcurrent protection to make something work.
Other OSHA rules (competency 1.10.3). OSHA sets the legal minimum for US workplaces. The rules a technician meets most often:
| Rule | What it requires |
|---|---|
| General Duty Clause (OSH Act 5(a)(1)) | The employer must keep the workplace free of recognized hazards that are causing or likely to cause death or serious physical harm, even where no specific standard covers the hazard. |
| Part 1910 vs part 1926 | 29 CFR 1910 covers general industry. Part 1926 covers construction work, defined as construction, alteration or repair (1910.12). The same task can fall under either, and the rules differ: fall protection starts at 4 ft in general industry (1910.28) and 6 ft in construction (1926.501). |
| Lockout/tagout (1910.147) | The six steps in section 3. For cord-and-plug equipment, unplugging it and keeping the plug under your exclusive control takes the place of a lock (the bench case). |
| Electrical work practices (1910.333) | De-energize live parts before working on or near them, unless that adds hazards or is infeasible; parts under 50 V to ground may stay live if there's no added burn or arc risk. Only qualified persons work on parts that are not de-energized. No conductive jewelry or clothing (rings, watch bands) that might contact exposed live parts, unless it is insulated or covered. |
| Electrical PPE and alerting (1910.335) | Electrical protective equipment for the body part at risk, nonconductive head protection, eye and face protection from arcs and flying debris, and insulated tools where a tool could touch exposed live parts. Signs, barricades and, when those aren't enough, an attendant to keep others away. |
| Construction power (1926.404(b)(1)) | Temporary 120 V, 15 and 20 A receptacles on construction sites need GFCI protection, or the employer runs an assured equipment grounding conductor program. |
Arc flash and NFPA 70E
An arc flash is the sudden release of electrical energy through the air when the insulation or spacing between conductors breaks down (NIOSH). Arc temperatures have been recorded as high as 35,000 °F; the light and heat cause burns, and the arc can heat the air so fast it makes a blast that throws molten copper and aluminum. Competency 1.10.1 asks for the protective equipment (PPE) this needs, and cites NFPA's Table 130.5(C).
That table comes from NFPA 70E, Standard for Electrical Safety in the Workplace. The current edition is 2024 (as of 2026); a 2027 edition is in development. Employer electrical-safety programs are built on it alongside OSHA's rules. It is a copyrighted standard, so this page teaches its ideas and does not reproduce its tables. Its first rule is to remove the hazard: put the equipment in an electrically safe work condition (disconnect it, lock and tag it, test for absence of voltage, and ground it if needed). Energized work is allowed only when de-energizing would create a greater hazard or is infeasible, the same test OSHA uses in 1910.333.
| 70E idea | What it means |
|---|---|
| Limited approach boundary | The distance from an exposed live part within which a shock hazard exists. |
| Restricted approach boundary | A closer distance where the chance of shock rises, from arc-over combined with an accidental movement. Qualified persons only. |
| Arc-flash boundary | The distance at which a person could receive a second-degree burn: an incident energy of 1.2 cal/cm². Inside it, arc-rated PPE is required. It is often farther out than the shock boundaries. |
| Risk assessment and Table 130.5(C) | The arc-flash assessment weighs how likely an arc flash is for the task as well as how severe it would be. Table 130.5(C), the one ETA names, lists tasks and whether an arc flash is likely; where it is, more protection such as PPE is required. Normal operation of properly installed and maintained equipment is generally not likely to cause one; operating a breaker for the first time after installation or maintenance is. |
| Choosing PPE | Either an incident-energy analysis (the result, in cal/cm², sets the arc rating the clothing and face protection need) or the PPE category method: categories 1 to 4, read from 70E's equipment tables (130.7(C)(15)), which give a category for each type of equipment within stated fault-current and clearing-time limits, with category 4 the most protective. |
| Energized electrical work permit | Written approval for justified energized work, recording the justification, the shock and arc-flash assessments, boundaries, PPE, how access is restricted, and the job briefing. It is not required for testing, troubleshooting or voltage measurement, but measuring is still energized work and still needs the assessment and PPE. |
| Equipment labels | Labels show at least the voltage, the arc-flash boundary and the PPE information, and must be durable enough for their location. |
Safety
Awareness, not qualification: knowing these terms does not make you a qualified person. OSHA lets only qualified persons, people trained to recognize and avoid the hazards, work on parts that have not been de-energized (1910.333(c)(2)). Follow your employer's electrical-safety program and training.Testing for absence of voltage is the step that turns "switched off" into "safe to touch"; the method is called live-dead-live. NFPA 70E has you use an adequately rated tester on each phase conductor or circuit part, phase to phase and phase to ground, at each point of work. If no live source is nearby (up a tower, for example), a battery-powered proving unit can serve as the known voltage.
On the exam
Live-dead-live: verify absence of voltage live-dead-live: prove the tester on a known live source, test the circuit, then prove the tester again. The last step catches a meter that failed during the test, because a dead reading from a dead meter looks exactly like a dead circuit. NFPA 70E requires the check before and after each test; OSHA 1910.333 requires it on circuits over 600 V.Meter CAT ratings
A meter's CAT rating (its measurement category under IEC 61010) tells you where on the power system it is built to survive a transient, a short high-voltage spike that can arc across inside an under-rated meter while it is in your hands. The rule of thumb: the closer you measure to the utility source, the more fault current is available and the higher the category you need. OSHA requires test instruments and their leads to be rated for the circuits they connect to, and inspected before use, and only qualified persons may do testing work on electric circuits (1910.334(c)). This supports competencies 1.10 and 8.3.
| Category | Where it applies |
|---|---|
| CAT I | Protected electronic equipment: circuits not connected directly to the mains, where little energy is available. It is rarely marked on meters; current maker guides list CAT II to IV. |
| CAT II | Single-phase receptacle-connected loads: appliances, portable tools, receptacle outlets and long branch circuits. |
| CAT III | The building's distribution: panels, breakers, feeders and bus, fixed equipment such as polyphase motors, and commercial lighting. |
| CAT IV | The origin of the installation: the utility service entrance, electricity meter, outdoor conductors and primary overcurrent protection. |
The voltage and the category both matter. Within one category, a higher voltage rating means a bigger test spike. A step up in category matters more, because the test comes from a lower source impedance. In Fluke's comparison, a CAT III 600 V meter is tested with a 6,000 V impulse from a 2 Ω source and a CAT II 1000 V meter with the same 6,000 V from 12 Ω. That is a peak of 3,000 A against 500 A, so the CAT III 600 V meter is the safer choice in a panel despite its lower voltage number. The voltage rating must still cover the circuit: a CAT III 300 V meter does not belong on a 480 V panel. Test leads carry their own rating, and the set is only as good as its lowest-rated part. Look for the mark of an independent testing lab (UL, CSA, TÜV); a CE mark is the maker's own declaration.
Trap
Field trap: a meter's CAT rating and NFPA 70E's PPE categories are unrelated numbers. CAT III on the meter says nothing about the clothing you need, and PPE category 2 says nothing about which meter to use.RF exposure and MPE
Competencies 1.8 and 1.10.2 cover RF transmitter hazards and MPE, maximum permissible exposure. Strong RF heats tissue. The eyes and testes are the most vulnerable, because they have little blood flow to carry heat away (FCC). Touching metal in a strong field (a guy wire, a fence, a vehicle) can also give an RF shock or burn; NIOSH found exactly that hazard at a high-power VLF transmitter site. Three documents set the limits:
| Document | What it is |
|---|---|
| FCC, 47 CFR 1.1310 | The binding US limits that FCC-licensed transmitter sites must meet, in two tiers (below). Based generally on NCRP Report No. 86 and ANSI/IEEE C95.1-1992. |
| IEEE/ANSI C95.1-2019 | The consensus safety standard, 0 Hz to 300 GHz. It sets limits for people permitted in restricted environments and for the general public in unrestricted ones. |
| OSHA, 29 CFR 1910.97 | A 10 mW/cm² guide (10 MHz to 100 GHz, averaged over any 0.1 hour). OSHA says it is written in voluntary language and has been ruled unenforceable, and points to the FCC rules and C95.1 instead. It still defines the RF warning sign, and the telecommunications rule (1910.268) forbids looking into an open waveguide connected to an energized source. |
Controlled vs uncontrolled. The FCC's occupational/controlled limits apply to people exposed because of their job who are fully aware of it (they have been told about the exposure and trained to control it) and can exercise control over it. Everyone else gets the general population/uncontrolled limits, including workers who aren't aware or can't control their exposure. Controlled limits average over 6 minutes, uncontrolled over 30 minutes.
Why the limit depends on frequency. The body absorbs RF most strongly near its whole-body resonance, about 70 MHz for a standing, ungrounded adult, so the limits are tightest from 30 to 300 MHz. From 300 to 1,500 MHz they rise in proportion to frequency, and above 1,500 MHz they are flat:
| Frequency | Controlled (mW/cm²) | Uncontrolled (mW/cm²) |
|---|---|---|
| 30–300 MHz | 1.0 | 0.2 |
| 300–1,500 MHz | f / 300 | f / 1500 |
| 1,500–100,000 MHz | 5 | 1.0 |
Worked example
An 800 MHz trunked site: at 851 MHz the controlled limit is 851 / 300 ≈ 2.84 mW/cm² and the uncontrolled limit is 851 / 1500 ≈ 0.57 mW/cm², five times lower. A 155 MHz VHF site sits in the flat 30–300 MHz band: 1.0 and 0.2 mW/cm².| Precaution | Why it works |
|---|---|
| Distance | In the far field, power density falls with the square of distance: doubling your distance cuts it to a quarter. |
| Stay out of the main beam | Exposure is highest directly in front of an antenna, in its main beam; at ground level below a base-station antenna it is much lower. Never stand in front of a dish or sector panel that may transmit. |
| Time and duty cycle | The limits are time-averaged. A push-to-talk radio transmits only while keyed, so a transmitter keyed half the time gives half the average exposure. |
| Reduce power or shut down | When work must happen in front of an antenna, arrange with the site owner to reduce power or shut the transmitter down. The FCC counts work practices like this, PPE and time averaging as ways to exercise control. |
| Signs and the waveguide rule | Obey RF warning signs and barriers, never look into an open waveguide connected to a live transmitter, and don't grab metal that may carry induced RF. |
On the exam
Exam point: MPE means maximum permissible exposure: the FCC's time-averaged RF exposure limit, in 47 CFR 1.1310. ETA's wording names OSHA and ANSI; in the US the binding limits for transmitter sites are the FCC's, in 47 CFR 1.1310, with a stricter general-population tier and a controlled tier for trained, aware workers.Fiber optic hazards
Competency 1.9 lists the hazards of optical fiber to the skin and eyes. There are three, and the Optical & Fiber guide covers handling.
| Hazard | Control |
|---|---|
| Invisible light (eyes) | Fiber links usually carry infrared light, which you cannot see, so a fiber end that looks dark tells you nothing. Never look into a fiber until you are sure no source is connected at the far end; check it with a power meter. Inspection microscopes should have infrared filters. |
| Glass shards (skin and eyes) | Cleaved fiber ends are extremely sharp and easily puncture skin, and the scraps are tiny. Put every scrap in a dedicated container (double-sided tape on the bench catches them), keep food and drink out of the work area, and wear safety glasses with side shields and gloves. |
| Chemicals | Splicing and termination use cleaners and adhesives. Even isopropyl alcohol, the usual cleaner, is flammable. |
Tool hazards
Competency 1.6 asks for the hazards of the tools you use in the shop and in the field. OSHA makes the employer responsible for the safe condition of every tool, including ones the employees bring (1910.242(a)). Soldering burns and fires are competency 5.1, on Soldering.
| Tool | Hazard and control |
|---|---|
| Corded power tools | Shock from damaged cords, broken ground pins and wet locations. Inspect the cord before you plug in, and never use a plug whose ground prong has been removed. On construction sites, GFCIs or an assured grounding program are required. |
| Saws, drills, grinders | Cuts and flying debris. OSHA requires guards on portable circular saws, and constant-pressure switches on hand-held circular saws and chain saws so the tool stops when you let go (1910.243). Leave guards in place. |
| Compressed air | Blown chips and debris. Use it for cleaning only below 30 psi, with chip guarding and PPE (1910.242(b)). |
| Hand tools near live parts | A screwdriver or pliers can bridge a live part to ground. Where a tool might touch exposed energized parts, use insulated tools (1910.335(a)(2)(i)). Take damaged tools out of service. |
| Oscilloscope on line-powered gear | Never "float" a scope by defeating its ground to measure a hot circuit: its chassis and connectors rise to whatever voltage the probe ground touches. Tektronix calls it unsafe and dangerous. Use a differential probe or an isolated-input scope. |
| Cutters and cleavers | Wire clippings and glass fly. Wear safety glasses with side shields. |
Ladders and working at heights
Competency 1.11 covers ladder handling (the ANSI A14 standards) and OSHA's working-at-heights rules: 29 CFR 1910.23 in general industry and 1926.1053 in construction.
| Rule | What to do |
|---|---|
| The 4-to-1 angle | Set the feet of an extension ladder out about one foot for every four feet of working length (the length from the feet to the top support): a horizontal distance of one-quarter of the working length (1926.1053(b)(5)(i)). That is about 75.5° from the ground. |
| 3 feet above the landing | A ladder used to reach a roof or upper level must extend at least 3 ft above the landing, so you have something to hold as you step on and off (1910.23(c)(11)). |
| Three points of contact | Two hands and one foot, or one hand and two feet, on the ladder at all times. Face the ladder, and don't carry anything that could throw you off balance; use a tool belt or haul tools up on a line. |
| Duty rating | Type III 200 lb, Type II 225 lb, Type I 250 lb, Type IA 300 lb, Type IAA 375 lb. Count yourself, your clothing and PPE, and every tool and part you carry. |
| Near power | Use a ladder with nonconductive side rails, such as fiberglass, wherever you or the ladder could touch exposed energized parts; never a metal ladder (1910.333(c)(7)). Unqualified workers keep at least 10 ft from overhead lines up to 50 kV. |
| Never | Stand on the top step or cap of a stepladder, move or extend a ladder while someone is on it, or use one with a defect: inspect it every shift and tag a damaged one "Do Not Use". |
Worked example
Setting a 20 ft ladder: with 20 ft of working length from the feet to the top support, put the feet 20 / 4 = 5 ft out from the wall. A 200 lb technician carrying 35 lb of tools and gear loads it to 235 lb, so a Type II (225 lb) ladder is too light; Type I (250 lb) is the minimum.Service vehicle safety
Competency 1.12 lists service-vehicle concerns: securing ladders and loads, flying objects, and driver screens. It matters because motor-vehicle crashes are the leading cause of work-related deaths in the US (NIOSH).
| Concern | What to do and why |
|---|---|
| Flying objects | In hard braking or a crash, anything loose keeps moving at the vehicle's old speed and becomes a projectile toward the cab. Keep tools and parts in bins, racks and tie-downs, and keep the cab clear of loose items. Federal cargo rules for trucks require tie-downs whose breaking strength is not exceeded at 0.8 g forward and 0.5 g rearward and sideways (49 CFR 393.102), so a 60 lb generator needs restraint against about 48 lb pushing forward. |
| Driver screen (cargo partition) | A strong partition between the cargo area and the cab keeps the load out of the driver's space when it shifts. ISO 27956 sets requirements and tests for van partitions and the lashing points used to tie cargo down. |
| Ladders and long loads | Lock or strap ladders to the rack at both ends and check them before you drive. Cargo must not fall, blow off or shift (49 CFR 393.100). On a commercial motor vehicle, a load sticking out more than 4 ft past the rear or 4 in past the sides needs red or orange fluorescent flags at least 18 in square (393.87); check your state's rule for other vehicles. |
On the job: three walk-throughs
Job practice, not exam content. These show how the rules above fit together on real work. Your employer's procedures and training come first; these are illustrations, not a qualification.
1. Lockout and live-dead-live at a radio shelter. You are replacing a hard-wired rectifier fed from a 240 V breaker in the shelter's panel.
- Find every source. The breaker, but also the battery plant, a generator or UPS, and any backfeed. OSHA's test must also catch induced voltage and backfeed.
- Open and lock. Open the breaker, then lock and tag it with your own lock.
- Pick and check the meter. At a branch panel and fixed equipment you need CAT III, with a voltage rating of at least 240 V. Inspect the meter and leads for damage.
- Live. Prove the meter on a known live source: a live circuit nearby, or a proving unit.
- Dead. At the rectifier's terminals, test each conductor to each other and to ground.
- Live again. Re-prove the meter on the same known source. Only now treat the circuit as de-energized.
- Stored and other energy. The rectifier's output capacitors and the DC battery plant are still live: discharge or isolate them, and wear battery PPE.
- Restore. Clear tools, tell the people affected, and remove your own lock yourself.
2. Choosing the meter for the measurement. Match the category to where the probes go, and the voltage rating to the circuit.
| Where you measure | Category you need |
|---|---|
| The outlet feeding a bench supply | CAT II or higher. |
| Breakers in a panel, or the feed to a hard-wired rectifier | CAT III or higher, rated above the panel voltage. |
| The utility meter base or service entrance at a tower site | CAT IV. |
| A radio's 13.8 V DC circuits | Not mains-connected (what older guides call CAT I); any CAT-rated meter covers it. |
3. A rooftop RF check before you work. Before you step in front of anything on a roof or tower:
- Know the antennas. Read the RF signs and the site's exposure information, and find every antenna that can transmit near your work spot.
- Know your tier. The controlled limits apply only if you have been informed and trained and can control your exposure. An untrained helper is in the general-population tier.
- Compare. At 851 MHz the limits are 2.84 (controlled) and 0.57 mW/cm² (uncontrolled). A measured 1.4 mW/cm² at your spot is within the controlled limit but over the general-population one, so the untrained helper should not stay there.
- Reduce. Stay out of the main beam, keep your distance, keep your time short, or arrange a power reduction or shutdown with the site owner.
- Don't touch or look. Never look into an open waveguide, avoid grabbing metal that may carry induced RF, and report any RF burn or shock.
Check yourself
Answer in your head first, then reveal.
What harms you in a shock: voltage or current?
current, not voltage, is what harms you
Under lockout/tagout, who may remove the lock?
the person who applies the lock is the only one who removes it
Which fire class is electrical, and which extinguisher fits it?
Class C is the electrical-fire class — use a non-conductive extinguisher (CO₂ or dry chemical)
Why keep one hand behind your back when probing live circuits?
One hand behind your back when probing live circuits keeps current from crossing your chest hand-to-hand.
Why discharge capacitors even after power is removed?
a charged filter capacitor in a power supply can hold a lethal charge long after power is removed
Practice this topic: Safety questions appear throughout the Study Hub quiz bank, and the key terms are in Flashcards.